Tartan Grid Ceilings

Typical K40 Specification
General description: Polyester painted steel
Lay-on tiles supported by Trim Strip grid.
Membrane material: Zintec steel tiles.
Size: A range of sizes is available up to
3 metres maximum length.
Thickness: 0.6mm minimum, with electroplated
zinc finish to BS EN 10143:1993.
Edge detail: Square edges to all sides.
Tile Face: Plain or Perforated (refer to
Perforation Patterns).
Finish: Electrostatically applied polyester
paint. High opacity formulation to an optimum thickness of 45 microns.
Colour: RAL 9010 20% gloss. Other BS or RAL
colours available on request. Specified colour to be controlled to Delta
E tolerance of 0.5.
Suspension system: Burgess Trim Strip Grid
system comprising plain trim strips with inturned long sides and out-turned
ends. To be supported from plain crossing boxes suspended from the soffit,
at 1500mm maximum centres, by M8 threaded suspension rods. Pre-punched
slots in the trim strips to locate on tabs on the vertical flanges of
crossing boxes. Trim strips and crossing boxes are provided with pre-punched
holes in side flanges to allow additional screw fixing on site.
Perimeter Trim: Extruded aluminium perimeter
channel trim, ref: ET181, colour Ral 9010 20% gloss.
Fire Performance: The ceiling system must
be fully tested in accordance with BS 476 Parts 6 and 7 and be of such
performance as to be designated CLASS 'O' under United Kingdom Building
Regulations.
Acoustic Performance: Full consideration
must be given to the acoustic contribution of the ceiling. An appropriate
acoustic insert is to be provided to achieve (see
acoustics):
Sound Absorption NRC ______
Sound Attenuation Dncw ______
Recommended Manufacturer: Burgess Architectural
Products Limited, Leics., England.
|